Data sheet
6ES7223-1BL32-0XB0
SIMATIC S7-1200, Digital I/O SM 1223, 16 DI/16 DO, 16 DI 24 V DC,
Sink/Source, 16 DO, transistor 0.5 A
General information
Product type designation
SM 1223, DI 16x24 V DC, DQ 16x24 V DC
Supply voltage
Rated value (DC)
24 V
permissible range, lower limit (DC)
20.4 V
permissible range, upper limit (DC)
28.8 V
Input current
from backplane bus 5 V DC, max.
185 mA
Digital inputs
● from load voltage L+ (without load), max.
4 mA; per channel
Output voltage
Power supply to the transmitters
● present
Yes
Power loss
Power loss, typ.
4.5 W
Digital inputs
Number of digital inputs
● in groups of
Input characteristic curve in accordance with IEC 61131,
type 1
16
2
Yes
Number of simultaneously controllable inputs
all mounting positions
— up to 40 °C, max.
16
horizontal installation
— up to 40 °C, max.
16
— up to 50 °C, max.
16
vertical installation
— up to 40 °C, max.
16
Input voltage
● Type of input voltage
DC
● Rated value (DC)
24 V
● for signal "0"
5 V DC at 1 mA
● for signal "1"
15 V DC at 2.5 mA
Input current
● for signal "0", max. (permissible quiescent current)
1 mA
● for signal "1", min.
2.5 mA
● for signal "1", typ.
4 mA
6ES72231BL320XB0
Page 1/2
1.19.2021
Subject to change without notice
© Copyright Siemens
Input delay (for rated value of input voltage)
for standard inputs
— parameterizable
Yes; 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms,
selectable in groups of four
for interrupt inputs
— parameterizable
Yes
Cable length
● shielded, max.
500 m
● unshielded, max.
300 m
Digital outputs
Number of digital outputs
● in groups of
16
1
Short-circuit protection
No; to be provided externally
Limitation of inductive shutdown voltage to
L+ (-48 V)
Switching capacity of the outputs
● with resistive load, max.
0.5 A
● on lamp load, max.
5W
Output voltage
● Rated value (DC)
24 V
● for signal "0", max.
0.1 V; with 10 kOhm load
● for signal "1", min.
20 V DC
Output current
● for signal "1" rated value
0.5 A
● for signal "1" permissible range, max.
0.5 A
● for signal "0" residual current, max.
10 µA
Output delay with resistive load
● "0" to "1", max.
50 µs
● "1" to "0", max.
200 µs
Total current of the outputs (per group)
horizontal installation
— up to 50 °C, max.
8 A; Current per mass
Relay outputs
Switching capacity of contacts
— with inductive load, max.
0.5 A
— on lamp load, max.
5W
— with resistive load, max.
0.5 A
Cable length
● shielded, max.
500 m
● unshielded, max.
150 m
Interrupts/diagnostics/status information
Alarms
● Diagnostic alarm
Yes
Diagnostics indication LED
● for status of the inputs
Yes
● for status of the outputs
Yes
Potential separation
Potential separation digital inputs
● between the channels, in groups of
2
Potential separation digital outputs
● between the channels, in groups of
1
● between the channels and backplane bus
500 V AC
Standards, approvals, certificates
CE mark
Yes
CSA approval
Yes
UL approval
Yes
cULus
Yes
FM approval
Yes
RCM (formerly C-TICK)
Yes
6ES72231BL320XB0
Page 2/3
1.19.2021
Subject to change without notice
© Copyright Siemens
KC approval
Yes
Marine approval
Yes
Ambient conditions
Free fall
● Fall height, max.
0.3 m; five times, in product package
Ambient temperature during operation
● min.
-20 °C
● max.
60 °C
● horizontal installation, min.
-20 °C
● horizontal installation, max.
60 °C
● vertical installation, min.
-20 °C
● vertical installation, max.
50 °C
Ambient temperature during storage/transportation
● min.
-40 °C
● max.
70 °C
Air pressure acc. to IEC 60068-2-13
● Storage/transport, min.
660 hPa
● Storage/transport, max.
1 080 hPa
Relative humidity
● Operation at 25 ℃ without condensation, max.
95 %
Connection method
required front connector
Yes
Mechanics/material
Enclosure material (front)
● Plastic
Yes
Dimensions
Width
70 mm
Height
100 mm
Depth
75 mm
Weights
Weight, approx.
310 g
last modified:
1/16/2021
6ES72231BL320XB0
Page 3/3
1.19.2021
Subject to change without notice
© Copyright Siemens